CABLE TYPE (Al-)
XLPE/PVC 6-35 kV
(Al-) XLPE/PVC 3,6/6 kV
Nominal area of conductor |
Conductor diameter |
Insulation thickness |
Outer sheath thickness |
Aprox. overall diameter |
Aprox. cable weight Copper |
Aprox. cable weight Aluminium |
mm 2 |
mm 2 |
mm |
mm |
mm |
kg/km |
kg/km |
16 |
10 |
2.5 |
1.8 |
18 |
470 |
370 |
25 |
16 |
2.5 |
1.8 |
19 |
635 |
475 |
35 |
16 |
2.5 |
1.8 |
20 |
750 |
530 |
50 |
16 |
2.5 |
1.8 |
21 |
890 |
585 |
70 |
16 |
2.5 |
1.8 |
23 |
1120 |
680 |
95 |
16 |
2.5 |
2.0 |
25 |
1425 |
810 |
120 |
16 |
2.5 |
2.0 |
26 |
1685 |
915 |
150 |
25 |
2.5 |
2.0 |
28 |
2065 |
1115 |
185 |
25 |
2.5 |
2.0 |
29 |
2425 |
1250 |
240 |
25 |
2.6 |
2.0 |
32 |
2975 |
1460 |
300 |
25 |
2.8 |
2.2 |
35 |
3715 |
1755 |
400 |
35 |
3.0 |
2.2 |
39 |
4700 |
2190 |
500 |
35 |
3.2 |
2.2 |
42 |
5660 |
2575 |
Nominal area of conductor |
Max. resistance of conductor at 20oC (DC) |
Max. resistance of conductor at
90oC (AC) |
Capacitance |
Charging current |
Trefoil Inductance |
Flat Inductance |
Cu
Ohm/km |
Al
Ohm/km |
Cu
Ohm/km |
Al
Ohm/km |
in ground |
in air |
mm 2 |
mF/km |
A/km |
mH/km |
mH/km |
mH/km |
16 |
1.1500 |
1.9100 |
1.4660 |
2.4480 |
0.201 |
0.23 |
0.459 |
0.783 |
0.598 |
25 |
0.7270 |
1.2000 |
0.9270 |
1.5400 |
0.233 |
0.26 |
0.426 |
0.738 |
0.564 |
35 |
0.5240 |
0.8680 |
0.6680 |
1.1100 |
0.261 |
0.30 |
0.406 |
0.710 |
0.545 |
50 |
0.3870 |
0.6410 |
0.4940 |
0.8220 |
0.294 |
0.33 |
0.376 |
0.670 |
0.515 |
70 |
0.2680 |
0.4430 |
0.3420 |
0.5680 |
0.335 |
0.38 |
0.356 |
0.639 |
0.495 |
95 |
0.1930 |
0.3200 |
0.2470 |
0.4110 |
0.383 |
0.43 |
0.342 |
0.610 |
0.480 |
120 |
0.1530 |
0.2530 |
0.1960 |
0.3250 |
0.414 |
0.47 |
0.333 |
0.595 |
0.471 |
150 |
0.1240 |
0.2060 |
0.1600 |
0.2650 |
0.453 |
0.51 |
0.321 |
0.574 |
0.459 |
185 |
0.0991 |
0.1640 |
0.1280 |
0.2110 |
0.492 |
0.56 |
0.312 |
0.557 |
0.450 |
240 |
0.0754 |
0.1250 |
0.0988 |
0.1620 |
0.528 |
0.60 |
0.302 |
0.536 |
0.440 |
300 |
0.0601 |
0.1000 |
0.0800 |
0.1300 |
0.555 |
0.63 |
0.294 |
0.515 |
0.432 |
400 |
0.0470 |
0.0778 |
0.0634 |
0.1019 |
0.585 |
0.66 |
0.288 |
0.495 |
0.426 |
500 |
0.0366 |
0.0605 |
0.0511 |
0.0804 |
0.603 |
0.68 |
0.282 |
0.480 |
0.421 |
S U S T A I N E D R A T I N G S
(A) |
Nominal area of conductor |
C O P E R |
A L U M I N I U M |
|
|
|
|
|
|
|
|
mm 2 |
in ground |
in ground |
in air |
in air |
in ground |
in ground |
in air |
in air |
16 |
129 |
140 |
121 |
147 |
100 |
109 |
94 |
114 |
25 |
166 |
180 |
158 |
193 |
129 |
140 |
123 |
151 |
35 |
198 |
214 |
192 |
234 |
154 |
167 |
150 |
183 |
50 |
234 |
252 |
231 |
282 |
182 |
197 |
179 |
219 |
70 |
287 |
306 |
289 |
351 |
223 |
240 |
224 |
274 |
95 |
343 |
362 |
353 |
428 |
266 |
284 |
274 |
333 |
120 |
388 |
408 |
406 |
490 |
302 |
321 |
315 |
383 |
150 |
434 |
445 |
461 |
551 |
338 |
354 |
360 |
433 |
185 |
489 |
496 |
528 |
628 |
382 |
397 |
413 |
496 |
240 |
564 |
564 |
622 |
734 |
443 |
455 |
490 |
585 |
300 |
635 |
628 |
718 |
838 |
500 |
508 |
565 |
669 |
400 |
714 |
676 |
830 |
942 |
570 |
561 |
662 |
768 |
500 |
800 |
746 |
948 |
1064 |
647 |
627 |
766 |
879 |
|
|
|