CABLE TYPE Al-XLPE/PVC self supported 10, 20 and 30 kV

Al-XLPE/PVC self supported 20/35 kV

CONSTRUCTION

 

3 x 50

3 x 70

3 x 95

3 x 120

3 x 150

             

PHASE CONDUCTOR

           

Conductor area

mm2

50

70

95

120

150

Conductor diameter

mm

8.4

10.0

11.8

12.9

14.6

Insulation thickness

mm

8.0

8.0

8.0

8.0

8.0

Diameter over isolation

mm

25.2

26.8

28.6

29.7

31.4

Metallic screen area

mm2

16

16

16

16

16

Outer sheath thickness

mm

2.0

2.0

2.2

2.2

2.2

Cable diameter

(approx. )

mm

33

34

36

37

39

             

MESSENGER

           

Conductor area

mm2

50

50

50

50

50

Steel strand diameter

mm

9.0

9.0

9.0

9.0

9.0

Outer sheath thickness

mm

1.2

1.2

1.2

1.2

1.2

Messenger diameter

mm

11.4

11.4

11.4

11.4

11.4

             
OVERHEAD NETWORK CABLE
Overall diameter

mm

76

79

84

86

89

Weight ( XHP )

kg/km

3645

4005

4505

4880

5295

Weight ( XHE )

kg/km

3385

3730

4190

4555

4955

             
ELECTRICAL PROPERTIES

Conductor resistance at 20°C (dc)

Ohm/km

0.641

0.443

0.320

0.253

0.206

Conductor resistance at 90°C (ac)

Ohm/km

0.822

0.568

0.411

0.325

0.264

Capacitance of cable

mF/km

0.118

0.131

0.144

0.153

0.165

Inductance of cable

mH/km

0.474

0.445

0.423

0.410

0.395

Current carrying capacity for overhead network cable directly exposed to solar radiation ( 30 °C )

A

179

220

267

305

345

Short-circuit current

(1 sec )

kA

4.7

6.6

9.0

11.4

14.1