CABLE TYPE Al-XLPE/PVC self supported 10, 20 and 30 kV

Al-XLPE/PVC self supported 6/10 kV

CONSTRUCTION

 

3 x 25

3 x 35

3 x 50

3 x 70

3 x 95

3 x 120

3 x 150

PHASE CONDUCTOR

Conductor area

mm2

25

35

50

70

95

120

150

Conductor diameter

mm

6.1

7.1

8.4

10.0

11.8

12.9

14.6

Insulation thickness

mm

3.4

3.4

3.4

3.4

3.4

3.4

3.4

Diameter over isolation

mm

13.7

14.7

16.0

17.6

19.4

20.5

22.2

Metallic screen area

mm2

16

16

16

16

16

16

16

Outer sheath thickness

mm

1.8

1.8

1.8

2.0

2.0

2.0

2.0

Cable diameter (approx. )

mm

21

22

23

25

27

28

30

MESSENGER

               

Conductor area

mm2

50

50

50

50

50

50

50

Steel strand diameter

mm

9.0

9.0

9.0

9.0

9.0

9.0

9.0

Outer sheath thickness

mm

1.2

1.2

1.2

1.2

1.2

1.2

1.2

Messenger diameter

mm

11.4

11.4

11.4

11.4

11.4

11.4

11.4

OVERHEAD NETWORK CABLE

Overall diameter

mm

52

54

57

61

65

67

70

Weight ( XHP )

kg/km

2050

2205

2400

2750

3080

3405

3745

Weight ( XHE )

kg/km

1900

2045

2230

2555

2865

3185

3510

ELECTRIC PROPERTIES

Conductor resistance at 20°C (dc)

Ohm/km

1.200

0.868

0.641

0.443

0.320

0.253

0.206

Conductor resistance at 90°C (ac)

Ohm/km

1.539

1.113

0.822

0.568

0.411

0.325

0.264

Capacitance of cable

mF/km

0.189

0.206

0.231

0.261

0.296

0.317

0.345

Inductance of cable

mH/km

0.423

0.403

0.389

0.372

0.347

0.336

0.326

Current carrying capacity for overhead network cable directly exposed to solar radiation ( 30 °C )

A

95

150

176

217

264

302

340

Short-circuit current (1 sec )

kA

2.4

3.2

4.7

6.6

9.0

11.4

14.1