PREMOULDED CABLE TERMINATIONS

Cable accessories

APPLICATION

It is used for terminating PVC, XLPE and EPR insulated single or three core cable 10, 20 and 35 kV, with aluminium or copper conductors.

CONSTRUCTION

Installation of termination is simple and quick. Number of insulating sheds for outdoor mounting, for one core: 4 for 10 kV, 8 for 20 kV and 10 for 35 kV. Dimensions and necessary data for selection of stress cone are shown in the following table.

.

Type of termination Diameter over insulation (mm) H D d Conductor cross-section (mm2)
  min max (mm) (mm) (mm) 10 kV 20 kV 35 kV
35PFD (PFG) 17
35PFD (PFG) 18
35PFD (PFG) 19
35PFD (PFG) 21
17,2
18,4
19,7
21,0
19,9
21,2
22,4
23,8
120 70
70
70
70
16
17
18,6
20
70
95
120
150
25
35
50
70
 
35PFD (PFG) 22
35PFD (PFG) 23
35PFD (PFG) 25
35PFD (PFG) 26
22,6
23,8
25,0
26,4
25,6
26,6
28,4
30,2
140 75
75
75
75
21
22,5
24
25
185
240
300
95
120
150
185
25
35
50
35PFD (PFG) 28
35PFD (PFG) 29
35PFD (PFG) 31
35PFD (PFG) 33
28,0
29,5
31,0
33,0
31,5
33,0
35,0
36,5
150 95
95
95
95
27
28,5
30
32
  240
300
70
95
120
150
35PFD (PFG) 34
35PFD (PFG) 37
35PFD (PFG) 39
34,5
37,0
39,0
38,0
40,5
42,5
160 100
100
100
33,5
36
38
    185
240
300

Indoor termination 35PFD consists of :

  • premoulded stress cone of EPDM rubber
  • insulating and thermoplastic tapes
  • cable lug (connector)

Outdoor termination 35PFG consists of:

  • premoulded stress cone of EPDM rubber
  • insulation sheds of EPDM rubber
  • earth collar
  • insulating and thermoplastic tapes
  • cable lug (connector)