Cable
accessories
APPLICATION
It is used for terminating PVC, XLPE and EPR insulated single or
three core cable 10, 20 and 35 kV, with aluminium or copper conductors.
CONSTRUCTION
Installation of termination is simple and quick. Number of insulating sheds for
outdoor mounting, for one core: 4 for 10 kV, 8 for 20 kV and 10 for 35 kV. Dimensions and
necessary data for selection of stress cone are shown in the following table.
.
Type of
termination |
Diameter
over insulation (mm) |
H |
D |
d |
Conductor
cross-section (mm2) |
|
min |
max |
(mm) |
(mm) |
(mm) |
10 kV |
20 kV |
35 kV |
35PFD (PFG) 17
35PFD (PFG) 18
35PFD (PFG) 19
35PFD (PFG) 21 |
17,2
18,4
19,7
21,0 |
19,9
21,2
22,4
23,8 |
120 |
70
70
70
70 |
16
17
18,6
20 |
70
95
120
150 |
25
35
50
70 |
|
35PFD (PFG) 22
35PFD (PFG) 23
35PFD (PFG) 25
35PFD (PFG) 26 |
22,6
23,8
25,0
26,4 |
25,6
26,6
28,4
30,2 |
140 |
75
75
75
75 |
21
22,5
24
25 |
185
240
300 |
95
120
150
185 |
25
35
50 |
35PFD (PFG) 28
35PFD (PFG) 29
35PFD (PFG) 31
35PFD (PFG) 33 |
28,0
29,5
31,0
33,0 |
31,5
33,0
35,0
36,5 |
150 |
95
95
95
95 |
27
28,5
30
32 |
|
240
300 |
70
95
120
150 |
35PFD (PFG) 34
35PFD (PFG) 37
35PFD (PFG) 39 |
34,5
37,0
39,0 |
38,0
40,5
42,5 |
160 |
100
100
100 |
33,5
36
38 |
|
|
185
240
300 |
Indoor termination 35PFD consists of :
- premoulded stress cone of EPDM rubber
- insulating and thermoplastic tapes
- cable lug (connector)
Outdoor termination 35PFG consists of:
- premoulded stress cone of EPDM rubber
- insulation sheds of EPDM rubber
- earth collar
- insulating and thermoplastic tapes
- cable lug (connector)
|