XHP 85 (-A)

CABLE TYPE (Al-)XLPE/SWA flat/PVC 6-35 kV

(Al-)XLPE/SWA flat/PVC 6/10 kV

Nominal area of conductor

Conductor diameter

Nom. cross-
sectional of metal. screen

Insulation thickness

Separation sheath thickness

Armour flat wire diameter

Outer sheath thickness

Aprox. overall diameter

Aprox. cable weight Copper

Aprox. cable weight Aluminium

No x mm2

mm

mm2

mm

mm

mm x mm

mm

mm

kg/km

kg/km

3 x 16

4.9

10

3.4

1.4

0.8 x 4

2.2

41

2675

2370

3 x 25

6.1

16

3.4

1.4

0.8 x 4

2.2

44

3155

2675

3 x 35

7.2

16

3.4

1.4

0.8 x 4

2.6

47

3710

3040

3 x 50

8.4

16

3.4

1.4

0.8 x 4

2.6

50

4280

3355

3 x 70

10.0

16

3.4

1.6

0.8 x 4

2.6

54

5180

3845

3 x 95

11.8

16

3.4

1.6

0.8 x 4

3.0

58

6380

4500

3 x 120

13.0

16

3.4

1.6

0.8 x 4

3.0

61

7345

4965

3 x 150

14.5

25

3.4

1.8

0.8 x 4

3.0

65

8640

5745

3 x 185

16.1

25

3.4

1.8

0.8 x 4

3.4

69

10080

6520

3 x 240

18.2

25

3.4

2.0

0.8 x 4

3.4

74

12085

7525

3 x 300

20.8

25

3.4

2.0

0.8 x 4

3.8

81

14725

8770


Nominal area of conductor

Max. resistance of conductor at 20oC (DC)

Max. resistance of conductor at
90oC (AC)

Capacitance Charging current Inductance

Cu

Al

Cu

Al

No x mm2

mF/km

A/km

mH/km

3 x 16

1.1638

1.9329

1.4836

2.4774

0.161

0.30

0.421

3 x 25

0.7357

1.2144

0.9381

1.5585

0.185

0.35

0.392

3 x 35

0.5303

0.8784

0.6760

1.1233

0.206

0.39

0.372

3 x 50

0.3916

0.6487

0.4999

0.8319

0.231

0.44

0.346

3 x 70

0.2712

0.4483

0.3461

0.5748

0.261

0.49

0.328

3 x 95

0.1953

0.3238

0.2500

0.4159

0.296

0.56

0.312

3 x 120

0.1548

0.2560

0.1984

0.3289

0.320

0.60

0.304

3 x 150

0.1255

0.2085

0.1619

0.2682

0.348

0.66

0.296

3 x 185

0.1003

0.1660

0.1295

0.2135

0.377

0.71

0.289

3 x 240

0.0763

0.1265

0.1000

0.1639

0.417

0.79

0.280

3 x 300

0.0608

0.1012

0.0810

0.1316

0.467

0.88

0.268


S T R U J N O   O P T E R E Æ E N J E (A)

Nominal area of conductor

C O P E R

A L U M I N I U M

No x mm2

in ground

in air

in ground

in air

3 x 16

114

109

89

84

3 x 25

148

142

115

110

3 x 35

175

170

136

132

3 x 50

207

203

161

158

3 x 70

252

250

196

194

3 x 95

301

302

234

235

3 x 120

341

346

265

269

3 x 150

383

392

298

305

3 x 185

429

443

336

347

3 x 240

493

515

388

405

3 x 300

554

582

437

461