XHP 84 (-A)

CABLE (Al-)XLPE/SWA/PVC 6-35 kV

(Al-)XLPE/SWA/PVC 20/35 kV

Nominal area of conductor

Conductor diameter

Nom. cross-
sectional of metal. screen

Insulation thickness

Separation sheath thickness

Armour wire diameter

Outer sheath thickness

Aprox. overall diameter

Aprox. cable weight Copper

Aprox. cable weight Alumin.

No x mm2

mm

mm2

mm

mm

mmf

mm

mm

kg/km

kg/km

3 x 50

8.4

16

8.0

1.8

3.15

3.4

77

9750

8825

3 x 70

10.0

16

8.0

2.0

3.15

3.8

81

11175

9840

3 x 95

11.8

16

8.0

2.0

3.15

3.8

85

12560

10680

3 x 120

13.0

16

8.0

2.0

3.15

3.8

88

13665

11315

3 x 150

14.5

25

8.0

2.2

3.15

4.0

93

15405

12510

3 x 185

16.1

25

8.0

2.2

3.15

4.0

96

16960

13400

3 x 240

18.2

25

8.0

2.2

3.15

4.0

100

19235

14715

3 x 300

20.8

25

8.0

2.2

3.15

4.0

106

22185

16230


Nominal area of conductor

Max. resistance of conductor at 20oC (DC)

Max. resistance of conductor at
90oC (AC)

Capacitance

Charging current

Inductance

Cu

Al

Cu

Al

No x mm2

mF/km

A/km

mH/km

3 x 50

0.3916

0.6487

0.4999

0.8319

0.127

0.80

0.429

3 x 70

0.2712

0.4483

0.3461

0.5748

0.140

0.88

0.405

3 x 95

0.1953

0.3238

0.2500

0.4159

0.156

0.98

0.384

3 x 120

0.1548

0.2560

0.1984

0.3289

0.166

1.04

0.372

3 x 150

0.1255

0.2085

0.1619

0.2682

0.179

1.12

0.361

3 x 185

0.1003

0.1660

0.1295

0.2135

0.191

1.20

0.350

3 x 240

0.0763

0.1265

0.1000

0.1639

0.209

1.31

0.337

3 x 300

0.0608

0.1012

0.0810

0.1316

0.231

1.45

0.321


S U S T A I N E D   R A T I N G S   (A)

Nominal area of conductor

C O P E R

A L U M I N I U M

No x mm2

in ground

in air

in ground

in air

3 x 50

203

213

158

166

3 x 70

245

260

191

202

3 x 95

292

313

228

243

3 x 120

330

356

258

277

3 x 150

368

401

288

313

3 x 185

413

453

325

356

3 x 240

473

525

375

415

3 x 300

529

505

421

472