XHE 49 (-A)

CABLE TYPE (A)2XS(F)2Y (XLPE) 6-35 kV

(A)2XS(F)2Y 6/10 kV

With copolymer coated Al tape

Nominal area of conductor

Conductor diameter

Nom. cross-sectional of metal. screen

Insulation thickness

Outer sheath thickness

Aprox. overall diameter

Aprox. cable weight Copper

Aprox. cable weight Aluminium

mm2

mm

mm2

mm

mm

mm

kg/km

kg/km

16

4.9

10

3.4

2.0

21

530

430

25

6.1

16

3.4

2.0

22

700

540

35

7.2

16

3.4

2.0

23

815

590

50

8.4

16

3.4

2.0

25

975

670

70

10.0

16

3.4

2.0

26

1210

770

95

11.8

16

3.4

2.0

28

1500

880

120

13.0

16

3.4

2.0

29

1760

995

150

14.5

25

3.4

2.0

31

2145

1190

185

16.1

25

3.4

2.0

32

2510

1135

240

18.2

25

3.4

2.2

35

3075

1155

300

20.8

25

3.4

2.2

38

3775

1815

400

23.8

35

3.4

2.2

41

4740

2230

500

26.3

35

3.4

2.2

44

5770

2590

Without copolymer coated Al tape

Nominal area of conductor

Conductor diameter

Nom. cross-sectional of metal. screen

Insulation thickness

Outer sheath thickness

Aprox. overall diameter

Aprox. cable weight Copper

Aprox. cable weight Aluminium

mm2

mm

mm2

mm

mm

mm

kg/km

kg/km

16

4.9

10

3.4

1.8

21

505

440

25

6.1

16

3.4

1.8

22

675

515

35

7.2

16

3.4

1.8

23

790

565

50

8.4

16

3.4

1.8

24

945

645

70

10.0

16

3.4

2.0

26

1180

740

95

11.8

16

3.4

2.0

28

1470

850

120

13.0

16

3.4

2.0

29

1730

960

150

14.5

25

3.4

2.0

30

2110

1155

185

16.1

25

3.4

2.0

32

2470

1295

240

18.2

25

3.4

2.0

35

3035

1515

300

20.8

25

3.4

2.2

37

3730

1770

400

23.8

35

3.4

2.2

40

4560

2050

500

26.3

35

3.4

2.2

43

5575

2405


Nominal area of conductor

Max. resistance of conductor at 20oC (DC)

Max. resistance of conductor at
90oC (AC)

Capacitance

Charging current

Trefoil Inductance

Flat Inductance

Cu
Ohm/km

Al
Ohm/km

Cu
Ohm/km

Al
Ohm/km

in ground

in air

mm2

mF/km

A/km

mH/km

mH/km

mH/km

16

1.1500

1.9100

1.4660

2.4480

0.161

0.30

0.496

0.790

0.635

25

0.7270

1.2000

0.9270

1.5400

0.185

0.35

0.462

0.747

0.600

35

0.5240

0.8680

0.6680

1.1100

0.206

0.39

0.439

0.717

0.577

50

0.3870

0.6410

0.4940

0.8220

0.231

0.44

0.411

0.679

0.549

70

0.2680

0.4430

0.3420

0.5680

0.261

0.49

0.389

0.648

0.527

95

0.1930

0.3200

0.2470

0.4110

0.296

0.56

0.368

0.618

0.507

120

0.1530

0.2530

0.1960

0.3250

0.320

0.60

0.357

0.600

0.496

150

0.1240

0.2060

0.1600

0.2650

0.348

0.66

0.345

0.582

0.484

185

0.0991

0.1640

0.1280

0.2110

0.377

0.71

0.335

0.565

0.473

240

0.0754

0.1250

0.0988

0.1620

0.417

0.79

0.325

0.545

0.464

300

0.0601

0.1000

0.0800

0.1300

0.467

0.88

0.310

0.520

0.448

400

0.0470

0.0778

0.0622

0.1010

0.524

0.99

0.300

0.499

0.439

500

0.0366

0.0605

0.0497

0.0795

0.571

1.08

0.291

0.482

0.429


S U S T A I N E D   R A T I N G S   (A)

Nominal area of conductor

C O P E R

A L U M I N I U M

linija.jpg (1114 bytes)

linija.jpg (1114 bytes)

mm2

in ground

in ground

in air

in air

in ground

in ground

in air

in air

16

127

139

126

147

99

108

97

113

25

163

179

164

191

127

138

128

148

35

195

212

199

232

152

165

155

180

50

231

249

240

278

179

194

186

216

70

282

302

298

346

219

237

232

270

95

338

359

364

423

263

282

283

330

120

383

404

417

484

299

319

325

379

150

429

443

473

546

334

352

369

428

185

483

494

540

621

378

395

423

489

240

556

560

635

723

437

452

499

573

300

604

622

730

826

494

505

575

659

400

703

676

841

934

563

561

672

759

500

786

743

956

1053

637

625

774

867